Home - Products & Services - Performance Monitoring Systems - InsuLogix™ H Hydrogen Detector

InsuLogix™ H Hydrogen Detector

Attention: open in a new window. PrintE-mail

Proven and Accurate Technology
The Weidmann InsuLogix™ H Hydrogen Detector employs proven thermal conductivity technology (TCD) with a measurement range of 0-10% H2.  The InsuLogix™ H Low Detection Limit (LDL) is equivalent to 50 PPM H2 in oil (or 1000 PPM in transformer headspace).
Benefits
  • Designed for Nitrogen headspace applications
  • Robust and tested technology platform
  • Easy field installation, no transformer outage required
  • Simple set-up and operation, no need for computer
  • The only fault detector that can be easily calibrated in field using standard gas
  • Responds to utilities’ demand for an economically priced H2 monitor
  • Adjustable H2 alarm set-points correlated to IEEE C57.104 headspace gas
  • Prepared for remote sampling interval modulation (manual or automatic)
Features
  • Capable of detecting H2 levels as low as ~50ppm in oil equivalent (1000ppm H2 in headspace)
  • User selectable test intervals
  • Two H2 alarm levels, one solid state relay
  • Manual alarm reset at unit
  • One 4-20mA output (H2)
  • Failure watchdog
  • Minimum and maximum H2 values retained
  • Backflow check valve in exhaust prevents contamination ingress under vacuum
  • Pure Nitrogen is used to set the detector’s baseline before each test
  • Optional: 4-20mA output recorder, USB memory stick
  • Optional: 4-20mA signal conversion and two way wireless data transmission, the information being visualized over secure Internet connection starting with satellite maps view of all substations equipped with InsuLogix H and scaling down to each monitor to see the status, the H2 trend, change the sampling interval or remotely force a test.
icon InsuLogixTM H Hydrogen Detector (206.08 kB)

Upcoming Events

Sep 21 2010 - Sep 21 2010 Load Tap changer (LTC) Principles, Maintenance & Diagnostics, High Voltage Supply / Waukesha Training Center, Dallas, TX

Sep 23 2010 - Sep 23 2010 Laboratory Methods for Fluid Diagnostic Testing, Duke Energy Plainfield Office, Plainfield, IN

Oct 19 2010 - Oct 21 2010 Annual Technical Conference, Tuscany Suites Hotel, Las Vegas, NV

Copyright © 2010 Weidmann Diagnostic Solutions Inc. All Rights Reserved.
A Member of the WICOR Group